35.8 Pulse width/Pulse period measurement function [M8075 to M8083, D8074 to D8097]
2. Cautions on use
The pulse width/pulse period measurement function and input interrupts can be used at the same time in a
same input terminal.
When a same input terminal is used by the pulse width/pulse period measurement function and the SPD,
DSZR or ZRN instruction, an operation error occurs when the instruction is executed.
The input terminal used for the pulse width/pulse period measurement function cannot be used for the
pulse catch function.
When a same input terminal is used by the pulse width/pulse period measurement function and a high
speed counter, a grammatical error occurs.
Make sure that the total frequency of four input channels is 50 kHz or less when using the pulse width/
pulse period measurement function.
When the pulse width/pulse period measurement function and a high speed counter are used together, the
overall frequency of the high speed counter is affected.