11 Applied Instructions (Data Operation)
11.3 ENCO / Encode
235
FXCPU Structured Programming Manual
[Basic & Applied Instruction]
11
Applied Instructions
(Data Operation)
12
Applied Instructions
(High Speed
Processing)
13
Applied Instructions
(Handy
Instruction)
14
Applied Instructions
(External FX I/O
Device)
15
Applied Instructions
(External Device
(optional device))
16
Applied Instructions
(External Device)
17
Applied Instructions
(Data Transfer 2)
18
Applied Instructions
(Floating Point)
19
Applied Instructions
(Data Operation 2)
20
Applied Instructions
(Positioning
Control)
Cautions
1) Instructions of pulse operation type are not provided in the FX0S, FX0 or FX0N PLC.
To execute pulse operation, make the instruction execution condition pulse type.
2) When two or more bits are ON in the data specified by , the low-order side is ignored, and only the
ON position on the high-order side is encoded.
3) When the command input is OFF, the instruction is not executed. Activated encode outputs are latched in
the previous ON/OFF status.
4) Some restrictions to applicable devices
S1:The FX
3G, FX3GC, FX3U and FX3UC PLCs only are applicable.
S2:The FX
3U and FX3UC PLCs only are applicable.