Mitsubishi Electronics FXCPU Video Game Controller User Manual


 
30 Applied Instructions (External Device Communication)
30.6 IVMC / Inverter Multi Command
723
FXCPU Structured Programming Manual
[Basic & Applied Instruction]
21
Applied Instructions
(Real Time
Clock Control)
22
Applied Instructions
(External Device)
23
Applied Instructions
(Extension
Function)
24
Applied Instructions
(Others)
25
Applied Instructions
(Block Data
Operation)
26
Applied Instructions
(Character
String Control)
27
Applied Instructions
(Data Operation 3)
28
Applied Instructions
(Data Comparison)
29
Applied Instructions
(Data Table
Operation)
30
Applied Instructions
(External Device
Communication)
Cautions
1) The instruction is provided in the FX3U and FX3UC PLCs Ver. 2.70 or later.
The instruction is provided in the FX
3G PLC Ver. 1.40 or later.
2) It is not permitted to use an "IVCK, IVDR, IVRD, IVWR, IVBWR
*1
or IVMC" instruction and a following
instruction for the same port:
- "RS or RS2" instruction
- "ADPRW" instruction
-"FLCRT
*1
, FLDEL
*1
, FLWR
*1
, FLRD
*1
, FLCMD
*1
or FLSTRD
*1
" instruction.
3) Two or more inverter communication instructions (IVCK, IVDR, IVRD, IVWR, IVBWR
*1
and IVMC) can be
driven for the same port at the same time.
4) Two devices are occupied respectively from the devices specified in and .
Make sure not to use such devices as to be used for other controls.
5) If a device number outside the allowable range due to indexing, etc. is specified in , the receive data
from the inverter is not stored in devices specified in . However, values set in and +1 may
be written to the inverter.
6) If any unspecified value is set in , unexpected data may be written to or read from the inverter,
and values stored in and +1 may be updated.
7) IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the
read status to the device specified in . Accordingly, the status written by IVMC instruction can be
read by a next or later read instruction (IVCK or IVMC).
8) Some restrictions to applicable devices
S1: The FX
3G, FX3GC, FX3U and FX3UC PLCs only are applicable.
S2: The FX
3U and FX3UC PLCs only are applicable.
*1. The instruction is not provided in the FX
3S, FX3G and FX3GC PLCs.
Applicable inverters
This instruction is applicable to the following inverters:
- FREQROL-E700 (February 2009 and later)
- FREQROL-D700 (Applicable in all)