• When is "K1024 (H400)"
The FLSTRD instruction reads the error information (error flag).
• When is "K1280 (H500)"
The FLSTRD instruction reads the error code and error code details for errors having occurred in the CF-
ADP. Up to 5 of the latest error codes and error code details can be stored.
Caution
1) It is not permitted to use an "FLCRT, FLDEL, FLWR, FLRD, FLCMD or FLSTRD" instruction and a
following instruction for the same port:
- "RS or RS2" instruction
- "ADPRW" instruction
- "IVCK, IVDR, IVRD, IVWR, IVBWR or IVMC" instruction
2) The instruction is provided in the FX
3U and FX3UC PLCs Ver. 2.61 or later.
Setting items Description
Error detection signal
b0 : The CompactFlash
TM
card is not mounted.
b1 : The CompactFlash
TM
card is full.
b2 : An error has occurred in the CF-ADP.
b3 : CF-ADP H/W error
b4 : CompactFlash
TM
card error
b5 to b15 : Not used
Setting items Description
Error code 1
+1
Error code details 1
+2
Error code 2
+3
Error code details 2
+4
Error code 3
+5
Error code details 3
+6
Error code 4
+7
Error code details 4
+8
Error code 5
+9
Error code details 5