Mitsubishi Electronics FXCPU Video Game Controller User Manual


 
30 Applied Instructions (External Device Communication)
30.2 IVDR / Inverter Drive
713
FXCPU Structured Programming Manual
[Basic & Applied Instruction]
21
Applied Instructions
(Real Time
Clock Control)
22
Applied Instructions
(External Device)
23
Applied Instructions
(Extension
Function)
24
Applied Instructions
(Others)
25
Applied Instructions
(Block Data
Operation)
26
Applied Instructions
(Character
String Control)
27
Applied Instructions
(Data Operation 3)
28
Applied Instructions
(Data Comparison)
29
Applied Instructions
(Data Table
Operation)
30
Applied Instructions
(External Device
Communication)
Cautions
For other cautions, refer to the Data Communication Edition manual.
1) The instruction is provided in the FX
3G PLC Ver. 1.10 or later.
2) It is not permitted to use an "IVCK, IVDR, IVRD, IVWR, IVBWR
*1
or IVMC" instruction and a following
instruction for the same port:
- "RS or RS2" instruction
- "ADPRW" instruction
-"FLCRT
*1
, FLDEL
*1
, FLWR
*1
, FLRD
*1
, FLCMD
*1
or FLSTRD
*1
" instruction
3) Two or more inverter communication instructions (IVCK, IVDR, IVRD, IVWR, IVBWR
*1
and IVMC) can be
driven for the same port at the same time.
4) Some restrictions to applicable devices
S1: The FX
3G, FX3GC, FX3U and FX3UC PLCs only are applicable.
S2: The FX
3U and FX3UC PLCs only are applicable.
*1. The instruction is not provided in the FX3S, FX3G and FX3GC PLCs.
PLC applicable version
The table below shows PLC versions applicable to each inverter.
PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700
FX3S Ver.1.00 or later
FX3G Ver.1.10 or later
FX3GC Ver.1.40 or later
FX3U Ver.2.20 or later Ver.2.32 or later
FX3UC Ver.1.00 or later Ver.2.20 or later Ver.2.32 or later