Mitsubishi Electronics FX3G Video Gaming Accessories User Manual


 
911
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-4 Applied Instruction Execution Time
31
FNC275-FNC279
Data
Transfer 3
32
FNC280-FNC289
High Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
Data move 3
275 ⎯⎯
276 ⎯⎯
277 ⎯⎯
278
RBFM
*1
50+900n 0.715
n :
Number of points transferred in
one operation cycle
RBFM
*2
244 + 103n 0.715
279
WBFM
*1
24 + 966n 0.715
n :
Number of points transferred in
one operation cycle
WBFM
*2
292 + 116n 0.715
*1. When the instruction is executed to a BFM in a special function block/unit for the FX0N/FX2N/FX2NC Series or
in the CC-Link/LT built in the FX
3UC-32MT-LT(-2)
*2. When the instruction is executed to a BFM in a special function block/unit for the FX
3U/FX3UC Series
High speed processing 2
280 HSCT 30.0 1.365
281 ⎯⎯
282 ⎯⎯
283 ⎯⎯
284 ⎯⎯
285 ⎯⎯
286 ⎯⎯
287 ⎯⎯
288 ⎯⎯
289 ⎯⎯
Extension file register control
290 LOADR 13.2 + 0.44n 0.325
291 SAVER 166n 6.4
292 INITR 17600n 0.325
293 LOGR 244 + 17.9n 0.715
294 RWER 46700n 0.325
n : Number of write target
sectors
295 INITER 17300n 0.325
296
to
299
⎯⎯
FX3U-CF-ADP
300 FLCRT 83.2 6.64
301 FLDEL 49.1 6.32
302 FLWR 77.9 + 2.9n 6.26
n : Number of written data
points
*3
303 FLRD 59.2 + 4.25n 6.18
n : Number of read data
points
*3
304 FLCMD 50.9 6.26
305 FLSTRD 50.9 6.24
*3. When 16-bit data is written or read.
FNC
No.
Instruction
Execution time in ON status (µs) Execution time in OFF status (µs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction