582
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
22 External Device – FNC170 to FNC179
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
Outline
This instruction writes a digital value to the analog block FX0N-3A
*1
or FX2N-2DA.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (WR3A)
m1 : Special block number
FX
3G/FX3U/FX3UC (D, DSS) PLC : K0 to K7
FX
3UC-32MT-LT(-2) : K1 to K7 (K0 indicates the built-in CC-Link/LT master.)
m2
: Analog output channel number
FX
0N-3A
*1
: K1 (ch 1)
FX
2N-2DA : K21 (ch 1) or K22 (ch 2)
: Data to be written
Specify a value output to the analog block.
FX
0N-3A
*1
: 0 to 255 (8 bits)
FX
2N-2DA : 0 to 4095 (12 bits)
*1. The FX
0N-3A is available only for the FX3U and FX3UC PLCs.
Operand Type Description Data Type
m1
Special block number
-FX3G/FX3U/FX3UC (D, DSS) PLC: K0 to K7
-FX
3UC-32MT-LT(-2) : K1 to K7
16-bit binary
m2 Analog output channel number 16-bit binary
Data to be written or word device storing data to be written 16-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P
m1 33333333 33333
m2 33333333 33333
3333333 333
P
FNC 177
WR3A
Mnemonic Operation Condition
16-bit Instruction
7 steps
WR3A
WR3AP
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
−
S
S
FNC177
WR3A
m1
m2
Command
input
S
S