FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.2 Supplement of Special Devices (M8000 - and D8000 -)
•FX3G PLCs
*1. Only a 40-point or 60-point type FX
3G PLC can be connected.
Number
Operation and function
FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP
Applicable
version
Ver.1.00 or later Ver.1.00 or later Ver.1.20 or later
1st analog special adapter
D 8280 Input data Ch1 Output data Ch1 Input data Ch1
D 8281
Input data Ch2 Output data Ch2 Input data Ch2
D 8282
Input data Ch3 Output data Ch3 Output data
D 8283
Input data Ch4 Output data Ch4 Not used
D 8284
Number of averaging times
for Ch1 (1 to 4095)
Not used
Number of averaging times
for Ch1 (1 to 4095)
D 8285
Number of averaging times
for Ch2 (1 to 4095)
Not used
Number of averaging times
for Ch2 (1 to 4095)
D 8286
Number of averaging times
for Ch3 (1 to 4095)
Not used Not used
D 8287
Number of averaging times
for Ch4 (1 to 4095)
Not used Not used
D 8288 Error status Error status Error status
D 8289
Model code: K1 Model code: K2 Model code: K50
2nd analog special adapter
*1
D 8290 Input data Ch1 Output data Ch1 Input data Ch1
D 8291
Input data Ch2 Output data Ch2 Input data Ch2
D 8292
Input data Ch3 Output data Ch3 Output data
D 8293
Input data Ch4 Output data Ch4 Not used
D 8294
Number of averaging times
for Ch1 (1 to 4095)
Not used
Number of averaging times
for Ch1 (1 to 4095)
D 8295
Number of averaging times
for Ch2 (1 to 4095)
Not used
Number of averaging times
for Ch2 (1 to 4095)
D 8296
Number of averaging times
for Ch3 (1 to 4095)
Not used Not used
D 8297
Number of averaging times
for Ch4 (1 to 4095)
Not used Not used
D 8298 Error status Error status Error status
D 8299