Mitsubishi Electronics FX3G Video Gaming Accessories User Manual


 
520
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
18 Floating Point – FNC110 to FNC139
18.21 FNC133 – ASIN / Floating Point Arc Sine
18.21 FNC133 – ASIN / Floating Point Arc Sine
Outline
This instruction executes the SIN
1
(arc sine) operation.
For handling of floating point, refer to Subsection 5.1.3.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 32-bit operation (DASIN and DASINP)
An angle is obtained from the sine value stored in [ +1, ], and stored to [ +1, ].
A real number can be directly specified as .
The sine value stored in [ +1, ] can be set within the range from 1.0 to +1.0.
The angle (operation result) stored in [ +1, ] is expressed in radians (from −π/2 to π/2).
For conversion between radians and degrees, refer to RAD (FNC136) and DEG (FNC137) instructions.
For RAD (FNC136) instruction, refer to Section 18.24.
For DEG (FNC137) instruction, refer to Section 18.25.
Error
An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in
D8067.
When a value specified in is outside the range from 1.0 to +1.0 (error code: K6706)
Operand Type Description Data Type
Head device number storing a sine value used in the SIN
1
(arc sine) operation.
Real number (binary)
Head device number storing the operation result
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD.b KnX KnY KnM KnS T C D R U\G VZModifyKH E ""P
33 3 3 3
33 3 3
Mnemonic Operation Condition
16-bit Instruction
DASIN
DASINP
Mnemonic Operation Condition
32-bit Instruction
9 steps
Continuous
Operation
Pulse (Single)
Operation
P
FNC 133
ASIN
D
S
D
S
D
S
S
D
D
S
Command
input
FNC133
DASIN
S
D
+1
Binary floating point
(real number)
+1
Binary floating point
(real number)
SIN
1
S
S
D
D
S
S
D
D
S