Mitsubishi Electronics FX3G Video Gaming Accessories User Manual


 
54
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.7 Types and Setting of Parameters
5 Assigning I/Os, setting the initial values for special units, and setting built-in
CC-Link/LT
1. Click the "I/O assignment" tab, and then set the I/O assignment, special function block/unit
names and built-in CC-Link/LT.
In order to use the "Special Unit" field, the "Special Function Block Settings" box in the "Memory
capacity" tab must be checked first.
When setting the station information in "Built-in CC-Link/LT Setup", it is necessary to put a
check mark to "Built-in CC-Link/LT Setup" on the "Memory capacity" tab.
*1. This area can be set only in FX3U/FX3UC PLCs.
*2. This item can be set only in the FX
3UC-32MT-LT-2.
Set item Contents of setting Setting range
I/O
Input relay
When the I/O range is set here according to the system configuration, those
inputs and outputs are checked in programming by GX Developer.
FX
3U/FX3UC:
0 to 377
FX
3G:
0 to 177
Output relay
FX
3U/FX3UC:
0 to 377
FX
3G:
0 to 177
Special Unit
*1
(It is necessary
to set the
memory
capacity.)
Unit No. This is the unit number of each special function block/unit.
Unit Name
Set the name of each special function block/unit whose initial values are to be
set.
32 half-width
characters
(or 16 full-width
characters)
Up
This button moves the cursor to the upper line (transposes the upper line).
Down
This button moves the cursor to the lower line (transposes the lower line).
Set...
This button displays "Special Function Block Settings" dialog box of the selected
unit number.
Refer to the next page.
Delete This button deletes the setting of the selected unit number.
Delete All This button deletes all existing setting in "Special Unit" field.
Read PLC data This button reads "Special Unit" field from the connected PLC.
Built-in
CC-Link/LT
Setup
*2
Set... This button displays the "Built-in CC-Link/LT Setup" dialog box.
This example shows a window in an
FX
3U/FX3UC PLC.