767
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
35 SFC Program and Step Ladder
35.1 SFC Program
31
FNC275-FNC279
Data
Transfer 3
32
FNC280-FNC289
High Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
35.1.10 Rule for creating branch circuit
Limitation in the number of branch circuits
In one parallel branch or selective branch, up to eight circuits can be provided.
When there are many parallel branches and selective branches, however, the total number of circuits per initial state is
limited to 16 or less.
It is not permitted to execute transfer or reset from a recombination line or state relay before recombination to a branch
state relay.
Make sure to provide a dummy state, then execute transfer or reset from a branch line to a separate state relay.
43
1
1 2 5 6 7 8 9 16
(Note)
8 circuits or less in 1 (parallel or selective) branch
16 circuits or less in total
23 4567 8
......