Mitsubishi Electronics FX3G Video Gaming Accessories User Manual


 
252
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
9 Move and Compare – FNC 10 to FNC 19
9.6 FNC 15 – BMOV / Block Move
9.6 FNC 15 – BMOV / Block Move
Outline
This instruction transfers (copies) a specified number of data at one time.
1. Instruction format
2. Set data
3. Applicable devices
S: This function is supported only in FX3U/FX3UC PLCs.
Explanation of function and operation
BMOV instruction transfers "n" points of data from to at one time.
If the device number range is exceeded, data is transferred within the possible range.
Transfer is enabled even if the transfer number range is overlapped.
To prevent overwriting before transfer of source data, data is automatically transferred in the order "[1] [2] [3]"
according to the number overlap status.
Operand Type Description Data Type
Transfer source data or device number storing data 16-bit binary
Transfer destination device number 16-bit binary
n Number of transferred points (including file registers) [n 512] 16-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD.b KnX KnY KnM KnS T C D R U\G VZModifyKH E ""P
33333333 S 3
3333333 S 3
n 333
P
FNC 15
BMOV
Mnemonic Operation Condition
16-bit Instruction
7 steps
BMOV
BMOVP
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
S
D
S
D
S
D
FNC 15
BMOV
n
"n" points
+n+n
+1+1
S
D
Command
input
S
D
S
D
S
D
D 9
D 10
D 11
D 10
D 11
D 12
D 11
D 12
D 13
D 10
D 11
D 12
X001
FNC 15
BMOV
D 10 D 9 K 3
X002
FNC 15
BMOV
D 10 D 11 K 3
[1]
[2]
[3]
[3]
[2]
[1]