12 - 62
MELSEC-Q
12 CONTROL SUB FUNCTIONS
[6] Precautions during control
(1) When step operation is carried out using interpolation control positioning
data, the step function settings are carried out for the reference axis.
(2) When the step valid flag is ON, the step operation will start from the
beginning if the positioning start signal is turned ON while "
Md.26
Axis
operation status" is "step standing by". (The step operation will be carried
out from the positioning data set in "
Cd.3
Positioning start No.".)
[7] Step function settings
To use the "step function", write the data shown in the following table to the
QD75 using the sequence program. Refer to section [4] "Using the step
operation" for the timing of the settings.
The set details are validated when written to the QD75.
Buffer memory address
Setting item
Setting
value
Setting details
Axis
1
Axis
2
Axis
3
Axis
4
Cd.34
Step mode
Set "0: Deceleration unit step" or "1: Data No.
unit step".
1544 1644 1744 1844
Cd.35
Step valid flag 1 Set "1: Carry out step operation". 1545 1645 1745 1845
Cd.36
Step start
information
Set "1: Step continue", depending on the stop
status.
1546 1646 1746 1846
Refer to Section 5.7 "List of control data" for details on the setting details.