11 MANUAL CONTROL
Restricted items
A manual pulse generator is required to carry out manual pulse generator
operation.
Precautions during operation
The following details must be understood before carrying out manual pulse
generator operation.
(1) The speed during manual pulse generator operation is not limited by the
"
Pr.8
Speed limit value".
(2) If the "
Cd.21
Manual pulse generator enable flag" is turned ON while the
QD75 is BUSY (BUSY signal ON), a warning will occur (warning code 100:
start during operation).
(3) If a stop factor occurs during manual pulse generator operation, the operation
will stop, and the BUSY signal will turn OFF.
At this time, the "
Cd.21
Manual pulse generator enable flag" will be left ON,
but manual pulse generator operation will not be possible. To carry out manual
pulse generator operation again, measures must be carried out to eliminate
the stop factor. Once eliminated, the operation can be carried out again by
turning the "
Cd.21
Manual pulse generator enable flag" ON OFF ON.
(4) Pulses will not be output if an error occurs when the manual pulse generator
operation starts.
REMARK
•
One QD75 module can be connected to one manual pulse generator.
•
The QD75 module can simultaneously output pulses to the axis 1 to axis 4 drive
units by one manual pulse generator.
(1-axis to 4-axis simultaneous operation is possible.)
Errors during operation
When the operation is stopped by the stroke limit (limit signal OFF), manual pulse
generator operation can be performed in the direction in which the limit signal turns
ON after an error reset. (An error will occur again if pulse input is provided in the
direction in which the limit signal turns OFF is turned ON.)
Upper/lower
limit signal
Manual pulse generator
operation possible
Manual pulse generator
operation not possible
V
Manual pulse
generator operation
ON
OFF