12 - 57
MELSEC-Q
12 CONTROL SUB FUNCTIONS
(3) Since the upper and lower limit values of the positioning address calculated
are outside of the range of Condition 2, use the positioning address within the
positioning range of Condition 2 (-2147483648 (µm) to 2147483647 (µm)).
Unit: µm
OP
0
-214748364.8 214748364.7
-241591910.4 241591909.5
Setting disallowed
Usable range in absolute
position detection system
Setting disallowed
2. Concept for the unit of degree
•
The positioning address is within the range 0° to 359.99999° at the position
to which a machine OPR was made.
When the OP position is not 0°, the range is also 0° to 359.99999°.
•
For positioning in the same direction, control from maximum to minimum
(for address increase: 359.99999° to 0°/for address decrease: 0° to
359.99999°) cannot be exercised. (See below)
0 0
359.99999 359.99999
OP
Unusable in absolute position detection
system.
Current value cannot be restored
properly at power supply on or resetting
Usable range in absolute position detection system
Unusable in absolute position
detection system.
Current value cannot be restored
properly at power-on or reset.
0
359.99999
( ~ )
•
When positioning is to be used in the absolute position detection system,
set the upper and lower limit values of the software stroke limit within the
range 0° to 359.99999°.