D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 97
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
P## RlyResp Type P## Disp as Dvc
Default: Refer to the program record sheet Default: No
Selection: Blank, 1 to 2 Selection: Yes or No
Blank
Point state does not affect the
operation of the corresponding relay.
Display CHECK DEVICE when this
point is off-normal.
Yes
1
Relay Follows Point: The relay
corresponding with this point
activates when the point is faulted to
any off-normal condition, even if the
point is bypassed. The relay
automatically resets when the point
returns to normal.
Do not display CHECK DEVICE
when this point is off-normal.
No
Use P## Disp as Dvc to cause the keypad to display
CHECK DEVICE when a point is off-normal or is
acknowledged after going into alarm.
2
Relay Latches: The relay
corresponding with this point latches
when the point enters into an alarm
condition. This relay provides a
steady output until the alarm is
acknowledged by a valid pass code,
then cleared from alarm memory with
an acknowledgment from the keypad.
Use this option to cause a relay (1 to 127 for
D9412GV2; 1 to 64 for D7412GV2) to respond when
a corresponding point with the same number (1 to
127) is faulted. This requires connecting D8129
OctoRelays to Zonex Bus 1 and Zonex Bus 2
(D9412GV2 only). Refer to the address settings on
the back of the D9412GV2/D7412GV2 Program
Record Sheet
(P/N: F01U003635).
Point 128 is reserved for use other than
an actual point. Only the first 127 points
can have an associated relay. Relays are
not available for Points 129 to 247.
Do not use the Chg Relays? function to
toggle relays reserved for special
functions. Special function relays are
Area and Panel Wide Relay functions as
well as relays assigned to CC Entr Key
Rly and P## RlyResp Type.
Use this function for devices with a dry
contact output that faults a point when
the device is in a trouble condition.
P## Local While Disarmed
Default: Refer to the program record sheet
Selection: Yes or No
Suppress Alarm, Trouble and
Restoral* Reports from this point
while the area to which it is assigned
is disarmed.
Yes
Send event reports occurring from
this point while the area is disarmed.
No
* Transmission of Restoral Reports continues if the alarm,
trouble, or bypass (by Sked, RPS, or Swinger bypass)
condition occurred when the area disarmed, and the point
restored.
To meet UL 864 requirements for
Central Station and Remote Station
applications, set this parameter to No.
Use this option to allow a Controlled point (P## Type
1, 2, 3), to report Alarms, Troubles, and Restoral
Reports only when the area is armed. This prompt
does not affect local annunciation.