Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 6.0 GV2AUX EN | 138
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Account Identification
Although RPS and the D5200 allow Path
# Ack Wait values of 1 to 4, the control
The D6600 Receiver can identify the network
accounts by either the IP address or the account
number received in the message sent from the control
panel. The account number sent in the message is
always the account number for Area 1. Although you
can program up to ten digits for the account number,
only eight digits are sent in the message to the D6600
Receiver.
panel interprets these entries as an entry
of 5.
Path # Retry Count
Default: 5
Selection: 0 to 255
0
COMM FAIL RG# SDI ### Events
are not generated.
6.6 SDI RPS/Enhanced
Communications Configuration
COMM FAIL RG# SDI ### Events
are generated after resending
Heatbeat Poll the number of times
selected for a given SDI path.
1 to 255
This section provides the necessary prompts for
configuring the SDI-Network Interface Module (NIM)
when using it for SDI RPS or SDI enhanced
communication applications.
Determines how many times the control panel
resends the Heartbeat Poll before declaring a path
failure and generating a COMM FAIL RG# SDI ###
(RG # = 1 to 4, SDI ### = 88 for Path 1, 89 for Path 2,
90 for Path 3, 91 for Path 4) Event.
Baud Rate
Default: 9600
Selection: 300, 1200, 2400, 4800, 9600, 14.4 K
If using IP Addresses as the
communication means for UL 864
Commercial Fire applications, program
this parameter as necessary.
The default settings meet or exceed the
UL specifications.
This item determines the communication baud rate for
the network interface module (NIM). Because the SDI
bus communicates at 9600 baud, keep this prompt at
9600 baud. Pressing the [SPACE] bar on the D5200
toggles through the available options.
Do not set this value to any setting other
than 9600 baud.
Path # Anti-Replay
Default: No
Parity/Stop
Selection:
Yes or No
Default: No/1
Anti-replay is a strategy that counters “replay” attacks.
This feature prevents a malicious attack that
substitutes a control panel or another network
interface module (NIM) from delivering counterfeit
events over a network in place of events sent by the
actual control panel. A replay attack occurs when
someone records a message sent over the network
by Device A, and replays this message at a later time
while pretending to be Device A.
Selection: No/1, No/2, Odd/1, Even/1
No/1 No parity, 1 stop bit.
No/2 No parity, 2 stop bits.
Odd/1 Odd parity, 1 stop bit.
Even/1 Even parity, 1 stop bit.
This prompt addresses two items: parity and the
number of stop bits for the network interface module
(NIM). Pressing the [SPACE] bar on the D5200
toggles through the available options.
If this function is required, you must also
enable the Substitution Monitor function
in the Conettix D6600 Communications
Receiver/Gateway. Refer to Substitution
Monitor in the Conettix D6600/D6100
Receiver Gateway Program Entry Guide
(P/N: 4998122702) for more details.
Do not set Path # Anti-Replay to Yes if
Path # Ack Wait is set to zero (0) for the
same path.
Set this item to No/1 when using the
External Modem feature.