Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 102
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
4.3 Point Assignments
When a sensor reset occurs, the control
panel does not accept alarms from any
These entries assign point indexes to Points 1 to 127,
129 to 247 for the D9412GV2 and Points 1 to 75 for
the D7412GV2, and assign the points to the areas.
Also included in this section are parameters used to
set the point’s debounce count, BFSK/Relay (for use
when transmitting in BFSK or assigning relays to
follow alarms for a group of points), and custom
keypad and report text for each point.
points with P## Resettable programmed
as Yes. During the 5-sec reset time,
alarms from these points are ignored.
Do not mix fire and intrusion devices on
the same powered loop.
P## Alarm Abort
Point Number
Default: Yes
Selection:
Yes or No
Default: 1
Selection: 1 to 127, 129 to 247
Yes If the point goes into an alarm
condition, the system delays the
alarm report for the amount of time
specified in the control panel-wide
parameter Abort Window.
Enter the point number you are programming. When
transmitting in Modem IIIa
2
, the three-digit point
number is reported to the D6500 or D6600. When
transmitting in BFSK, you must assign a zone number
in BFSK/Relay.
No If the point goes into an alarm
condition, alarm reports are sent
immediately.
Point number 128 is reserved for
supervising Zonex 1.
This parameter allows points with the associated
Point Index to delay a Burglar Alarm (non-fire) event
for the time period specified in the Abort Window. An
alarm is aborted by performing an alarm silence
operation at a keypad showing the burglar alarm
condition before this time elapses.
When an alarm is successfully aborted, the keypad
shows an optional ALARM NOT SENT message and
no event is sent or written in the control panel event
log. Refer to
CC# Abort Display on page 56.
For SIA CP-01 Compliance:
P## Alarm Abort can be set to Yes or No.
This feature does not apply to Fire Alarms
or invisible point alarms.
Point number 248 is reserved for
supervising Zonex 2.
P### Point Index
Default: Refer to the program record sheet
Selection: Blank (00) to 31
This entry selects one of the 31 P## Index codes that
define the point’s characteristics and determines how
the control panel responds to various point conditions.
Blank (00) disables the point.
Missing Point Report
If a Point Index is assigned to a point that has an
incorrect address or that is not connected to the point
bus, a Missing Point Report occurs.
When a POPIT is missing, the control panel
generates the following responses based on the point
type:
Fire points generate missing trouble responses.
Non-fire 24-hour points generate missing alarm
responses.
Non-fire, non 24-hour points generate missing
alarm responses while armed, and trouble
responses while disarmed. Exception: Non-fire,
non-24-hour points with a point response of 9 to
D generate a missing alarm response while
disarmed.