Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 82
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Battery Trouble Summary Fire
Default: Blank Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Selection Blank, 1 to 128 (1 to 64 for
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing condition.
This relay automatically resets when battery power
restores.
Use this relay to create audible
annunciation. Enable the keypad’s
trouble sounders for all applications
except commercial fire systems.
Phone Fail
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a telephone line failure occurs. A time
must be entered in Ph Supv Time (refer to Section
2.2
Phone Parameters on page 12) for this relay to
activate. This relay resets automatically when restoral
of the phone line(s) occurs.
Comm Fail
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a control panel cannot communicate a
report after making ten attempts to each routing
destination. At the same time, COMM FAIL RT ##
displays at the keypad. This relay automatically resets
when a report is sent successfully.
Use this relay to report primary digital
report failure to an alternate
communication device.
Log % Full
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Enter the number of the relay that activates when the
log reaches the programmed percentage of its
capacity as programmed in the Log % Full prompt
under GV2MAIN. This relay provides a steady output
until a Get Log and Set Pointer is executed from the
remote programming software (RPS).
: D7412GV2), A, B, or C
Enter the number of the relay that activates when any
Fire point in the system (P## Type 0, P## Fire Yes)
enters into alarm. This relay provides a steady output
until all Fire points in the system return to normal.
Refer to
on page 139Fire Summary Sustain for
details on alternate operation.
Summary Alarm
Default: Blank
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
Enter the number of the relay that activates when a
Non-fire point enters into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid pass code, then cleared from alarm memory with
an acknowledgment at the keypad.
This relay does not activate for silent and
invisible alarms.
Summary Fire Tbl
Default: Blank
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
Activates when any Fire point in the control panel is in
trouble, or if a Fire Supervision point is missing. This
relay provides a steady output until all Fire points
restore to a normal condition.
Summary SupFire
Default: Blank
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off-
normal). This relay provides a steady output until all
Fire Supervisory points are restored to a normal
condition.