D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 11
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
2.0 GV2MAIN
Use GV2MAIN programming module to define the
operating characteristics that affect panel-wide
functions. This module has nine programming
categories:
Phone
Phone Parameters
Routing
Enhanced Communications
Area Parameters
Keypad
User Interface
Function List
Relay Parameters.
2.1 Phone
The control panel can dial as many as four different
telephone numbers when sending event reports. All
telephone numbers use the same receiver format.
Refer to Section
2.3 Routing on page 15 for
information about event report routing and
communication protocols.
When using PSTN telephone lines,
program two telephone numbers to
meet UL 864 requirements.
Phone 1
Default: Blank
Selection:
Up to 24 characters (do not enter
[SPACE])
0 to 9 Numbers 0 through 9
C 3-sec pause
D 7-sec dial-tone detection
# or * Used for the same purpose as
pressing this key on a telephone
keypad when manually dialing. For
example, an asterisk (*) may be
needed to access your long distance
service. Do not use these characters
when pulse dialing.
Blank Control panel dials no phone number.
Programming this item Blank does
not disable phone routing. To disable
reporting to this phone, refer to
Section
2.3 Routing on page 15.
This is the telephone number the control panel dials
to contact the central station receiver when sending
event reports. This number is Phone 1 referred to in
the prompts in Section
2.3 Routing on page 15.
The control panel is programmed with a 7-sec dial
tone detect period. When a dial tone is detected or
the waiting period ends, the control panel begins to
dial. To extend the dial tone detect period, place a D
before the phone number. To insert a pause during or
after dialing, use C in the number sequence. For
example, if the control panel hangs up before it hears
the Modem IIIa
2
ACK tone from the D6500 or D6600,
program extra Cs after the phone number. The
control panel waits on line for three extra seconds for
each C programmed.
Enter up to 24 of the characters shown in the Phone
1 table to define dialing characteristics.
Using both phone-data entry lines: The
first line of the phone number data entry
line must be filled (twelve characters)
before you press [ENTER] to move to the
second line. If you enter characters on
the second line, and the first line has less
than twelve characters, the second line
clears when you press [ENTER].
For SIA CP-01 Compliance
Call Waiting Disable
If the telephone system at the installation site uses
the Call Waiting feature, ensure that the backup
telephone reporting number is programmed to
disable Call Waiting.
If you program the primary phone number with a
sequence to temporarily disable Call Waiting
(typically *70 pause, but verify with the phone service
provider) followed by the phone number, you should
program the backup phone number without the Call
Waiting cancel sequence. If the subscriber cancels
Call Waiting without notifying their alarm installing
company, the control panel can still send reports
using the backup number.
Dialing a Call Waiting sequence on a
non-Call Waiting line prevents the system
from dialing the central station receiver
successfully.
Example: If the central station telephone
number is 555-1234, and the backup
Route Group destination is Phone 2,
program Phone 2 with the following
sequence: 70C5551234.