D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 103
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
POPIT modules monitor their sensor loops for three
conditions: loop normal, loop open, and loop shorted.
They send reports on these three conditions to the
control panel. The control panel uses point
programming to interpret the sensor loop information
sent by the POPITs and to make the appropriate
system response.
P### BFSK/Relay
Default: Refer to the program record sheet
Selection: 0 to 9
Use this option to:
Determine the point number sent in BFSK format
when this point is faulted.
P### Area Assign
Activate a relay when the point is faulted, even if
the control panel is programmed for Modem IIIa
2
reporting format. Refer to
Default: 1
Table 32.
Selection: 1 to 8
The areas are numbered 1 to 8. Select the area
number to which the point is assigned.
P### Debounce
Default: 2
Selection
:
1 to 15
1 .300 sec
2 .600 sec
3 .900 sec
4 1.2 sec
5 1.5 sec
6 1.8 sec
7 2.1 sec
8 2.4 sec
9 2.7 sec
10 3.0 sec
11 3.3 sec
12 3.6 sec
13 3.9 sec
14 4.2 sec
15 4.5 sec
The debounce count is the number of times the
control panel scans a point before generating an
alarm. Scan cycles are 300 ms.
For appropriate settings consult the manufacturer’s
instructions for the device connected to this point.
Use an entry of two or higher. Interior
Follower points need a Debounce value
of at least three.
Door points assigned to D9210B
modules need a Debounce value of at
least four.
BFSK/Relays do not activate for Fire
Supervisory or Non-Fire Supervisory
points.
Table 32: P### BFSK/Relay Codes/Relays
Faults Relay
D8129 on
Zonex Bus 2
for D9412GV2*
D8129 on
Zonex Bus 1
for D7412GV2*
BFSK Code
1 73 9
2 74 10
3 75 11
4 76 12
5 77 13
6 78 14
7 79 15
8 80 16
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on)
Local annunciation on the keypads, Local
Printer reports, and the View Log show
the actual point number (1 to 247), not
the BFSK report code
Do not assign a BFSK or relay to Invisible
points. To avoid activating one of the
associated relays, program this prompt
as 0.
On the D9412GV2, do not use Relays 73
through 80 for Area or Panel-Wide Relay
function when this prompt is enabled for
Table the corresponding points. Refer to
32.
On the D7412GV2, do not use Relays 9
through 16 for Area or Panel-Wide Relay
function when this prompt is enabled for
Table the corresponding points. Refer to
32.