Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 104
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
4.4 COMMAND 7 and COMMAND 9
Two relays can activate when this point
enters into alarm if the P## Rly Resp
These entries assign point indexes, BFSK report
code, BFSK relay that activates, and the text for the
COMMAND 7 and COMMAND 9 keypad functions.
Type for this point is programmed.
Use these codes to activate relays on the
D8129 OctoRelay (or C8137 Transmitter
Interface). You can assign the same code
to several points providing a summary
zone alarm output. When the point enters
into alarm, the relay activates. When the
alarm is acknowledged and is no longer
scrolling in the keypad display, the relay
resets.
CMD7 Point Index
Default: 31
Selection: Blank (00) to 31
This entry selects one of the 31 P## Index codes that
define how the control panel reacts when a
COMMAND 7 is initiated.
P### Point Text
Default: Refer to the program record sheet
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters (A to Z) in capital letters.
Enter up to sixteen characters of text to describe the
point. This point text is shown at keypads, if the point
is programmed as visible, and sent to the D6500 or
D6600 when transmitting in Modem IIIa
2
format (if it is
a reporting point).
Include the point number in custom point text. This
helps the user when viewing events, creating
bypasses, and so on. It can also simplify
troubleshooting.
When a D1260 Keypad is installed on the
system, the point text for Points 240 to
247 can be used for Area Name Text for
Areas 1 to 8, respectively. Refer to Table
33:
Table 33: Point Text for Points 240 to 247
Point Text Corresponding Area Name Text
Point 240 Area 1
Point 241 Area 2
Point 242 Area 3
Point 243 Area 4
Point 244 Area 5
Point 245 Area 6
Point 246 Area 7
Point 247 Area 8
The point index code used for
COMMAND 7 must not be used for any
other points on the system.
If the point index for COMMAND 7 has
Fire points programmed as Yes, this
causes access control doors to unlock if
Fire Unlock is also programmed as Yes.
Refer to the D9210B Program Entry
Guide
(P/N: 32207).
CMD7 BFSK/Relay
Default: 1
Selection: 0 to 9
This entry selects one of the digits shown for reporting
in BFSK or for activating relays 73 to 80 (on the
D9412GV2) or relays 9 to 16 (for the D7412GV2)
when COMMAND 7 is initiated (refer to the
P### BFSK/Relay prompt on page
103).
COMMAND 7 does not activate the
Summary Fire Alarm relay.
CMD7 Point Text
Default: [COMMAND][7]
Up to sixteen alphanumeric
Selection:
characters
Enter alphabetic characters A to Z in capital letters
Enter up to sixteen characters of text to describe the
point. This point text appears at keypads (if the point
is programmed as visible) and sent to the D6500 or
D6600 when transmitting in Modem IIIa
2
format (if it is
a reporting point).