D9412GV2/D7412GV2 | Program Entry Guide | 1.0 Introduction EN | 9
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Table 5: UL 864 Programming Requirements (continued)
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Refer to
Page:
Area 1 Area On
Required to
send system
status reports
Yes / No Set to Yes 36
A# Delay Res Yes Yes / No Set to Yes 38
Verify Time Yes 10 to 60 sec 60 sec 38
Area # Fire Time Yes 1 to 90 min 5 min (check with AHJ) 42
CC# Supervised Yes Yes / No Set to Yes 51
CC# Trouble Tone Yes Yes / No Set to Yes 54
CC# Scroll Lock Yes Yes / No Set to Yes 56
Remote Program
Disable /
Enable
Blank, E, or P Set to P 65
A# Fire Bell Yes
A,B,C, 1 to 128,
Blank
Program with a relay 79
A# Reset Sensors Yes
A,B,C, 1 to 128,
Blank
Program with a relay 79
U### Area # Auth Yes 1 to 8, Blank
Program an Authority
Level for the Fire Area
85
U### Passcode Yes
3-, 4-, 5-, or 6-digit
passcode
Must program at least
one passcode
86
P## Silent Bell No Yes / No Set to No 94
P## Invisible Pt No Yes / No Set to No 95
P## Local While
Disarmed
No Yes / No Set to No 97
P## Local While Armed No Yes / No Set to No 98
P## Disable Rst No Yes / No Set to No 98
P## Bypassable No Yes / No Set to No 99
P## Swinger Byps No Yes / No Set to No 100
P## Fire Point Yes Yes / No Set to Yes 101
P## Resettable Yes Yes / No As required 101
Sked## Function Code Required 1 to 11, 13 to 28 Sked Function Code 9 116
Sked## Defer Test No Yes / No Set to No 118
Sked## Hourly Test
(Report?)
No Yes / No Set to No 118
Sked## Time Enter valid time 00:00 to 23:59 00:00 to 23:59 123
Sked## Date No mm/dd Set to No 123
Sked## Sunday Yes Yes / No Set to Yes 123
Sked## Monday Yes Yes / No Set to Yes 123
Sked## Tuesday Yes Yes / No Set to Yes 123
Sked## Wednesday Yes Yes / No Set to Yes 123
Sked## Thursday Yes Yes / No Set to Yes 123
Sked## Friday Yes Yes / No Set to Yes 123
Sked## Saturday Yes Yes / No Set to Yes 123
Sked## Xept On Holiday No Yes / No Set to No 124