Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 1.0 Introduction EN | 8
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
1.5 Guide to UL 864 Programming Requirements
This section identifies the programming requirements you must make in order to comply with UL 864
Commercial Fire applications.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 5.
Table 5: UL 864 Programming Requirements
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Refer to
Page:
If using two phone lines:
Phone 1 through 4 Yes 24 characters
Program a valid phone
number
11 to 12
Phone Supervision Yes 0 to 240 sec 10 to 200 sec 14
Alarm On Fail No Yes / No Set to No 14
Buzz On Fail Yes Yes / No Set to Yes 15
Two Phone Lines Yes Yes / No
Set to Yes when using
PSTN communications.
15
Expand Test Report Yes Yes/No Set to Yes 15
Fire Reports Yes Yes / No Set to Yes 18
R# Fire Supervisory
Missing
Required Yes/No Set to Yes 18 (Table 10)
Test Reports Yes Yes / No Set to Yes 19
AC Fail Report Yes Yes / No Set to Yes 20 (Table 14)
AC Restoral Report Yes Yes / No Set to Yes 20 (Table 14)
Battery Missing Report Yes Yes / No Set to Yes 20 (Table 14)
Low Battery Report Yes Yes / No Set to Yes 20 (Table 14)
Battery Restoral Report Yes Yes / No Set to Yes 20 (Table 14)
RG#1 Primary SDI Yes Yes / No Set to Yes 25
RG#1 Backup SDI Yes Yes / No Set to Yes 25
R# Service Start Report Required Yes / No Set to Yes 22 (Table 18)
R# Service End Report Required Yes / No Set to Yes 22 (Table 18)
R# Fire Walk St Report Required Yes / No Set to Yes 22 (Table 18)
R# Fire Walk End Report Required Yes / No Set to Yes 22 (Table 18)
R# Walk Test St Report Required Yes / No Set to Yes 22 (Table 18)
R# Walk Test End Report Required Yes / No Set to Yes 22 (Table 18)
RG #1 Primary Device N/A 1 to 4 Must have 1 to 4 25
RG #1 Backup Device N/A 1 to 4 Must have 1 to 4 25
AC Fail Time Yes 1 to 90 Enter 61 28
AC Fail Display Yes 10 to 300 sec 10 to 200 sec 29
AC Tag Along Yes Yes / No Set to Yes 30
AC/Battery Buzz Yes Yes / No Set to Yes 30
Bat Fail/Res Rpt Yes Yes / No Set to Yes 30