Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 5.0 RADXSKED EN | 114
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
UW# Sunday UW# Group Enable
Default: No Default: 00:00
Selection: Yes or No Selection: HH:MM (hours and minutes)
This prompt, and the next six day of the week
prompts, select the days of the week that the User
Group Window is active.
Refer to the W# Sunday prompt in
Section 5.1.1 Opening and Closing on
page 106 for more information about
programming this prompt.
UW# Monday
Default: No
Selection: Yes or No
UW# Tuesday
Default: No
Selection: Yes or No
UW# Wednesday
Default: No
Selection: Yes or No
UW# Thursday
Default: No
Selection: Yes or No
UW# Friday
Default: No
Selection: Yes or No
UW# Saturday
Default: No
Selection: Yes or No
This prompt must be programmed if this
User Group Window is assigned to a user
group.
Enter the time of day when the window starts.
Beginning at this time, users assigned to this
window’s group can use their pass codes. The
window goes into effect at the beginning of the
minute. Make entries using a 24-hour clock (for
example, 7:00 AM is entered as 07:00, 2:45 PM is
entered as 14:45).
If the window must activate on the same day that you
program it, reboot the control panel to activate it
immediately.
UW# Group Disable
Default: 00:00
Selection: HH:MM (hours and minutes)
This prompt must be programmed if this
User Group Window is assigned to a user
group.
Enter the time of day when the window ends. This
time marks the end of the period in which users
assigned to this window’s group can use their pass
codes. The window stops at the end of the minute.
Make entries using a 24-hour clock (for example,
7:00 AM is entered as 07:00, 2:45 PM is entered as
14:45).
To disable the window, both the hours and minutes
spaces must be blank.
Do not program a single window to cross the
midnight boundary. The window stop time must be
later than the window start time.