Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 80
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
A# Watch Mode
When sharing one relay to reset sensors
in two or more areas, you must program
Default: Blank
the following. Failure to do so causes
TROUBLE PT ### for all point types
programmed as P## Resettable.
CC # Scope must include all areas
that share the relay.
L## Reset Sensors authority must be
assigned to the pass code that
activates the COMMAND 47 or Reset
Sensor function.
A# Verify Time must be the same
number of seconds for all areas that
share the relay.
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
This relay activates when a Controlled point
programmed for P## Watch Point is faulted in the
specified area while the area is in Watch Mode and
the point is not armed. It remains active for 2 sec after
each point is faulted.
A# Area Armed
Default: Blank
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
To meet UL 864 requirements, set A#
Reset Sensors to a value other than
Blank.
This relay activates when the specified area becomes
Master Armed. The exit delay must expire before the
relay activates. The relay remains active until the area
disarms. It does not deactivate during the entry delay
time.
A# Fail to Close
If multiple areas use the same relay, the relay
activates when all areas are armed. It deactivates
when the first area disarms.
Default: Blank
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
The A# Area Armed relay function can provide visual
feedback at a key switch station. Attach a LED to the
output of a D8129 Module programmed for this
function.
This relay activates when the Closing Window expires
for the specified area. It remains active until midnight,
another Closing Window starts, or the control panel
resets, whichever occurs first. When Perimeter Relay
(refer to page
Area 7 Area 8
Refer to
and in Alternate Functions for
A# Silent Alarm
142) is set to Yes, the A# Fail to Close
prompt becomes A# Perimeter Relay when using
firmware version 7.07 and later. Refer to Area 7 in
on page 81 for additional relay
functions when using firmware version 7.06 or earlier.
Alternate Functions for A# Silent Alarm on page 81 for
additional relay functions when using firmware version
7.06 and earlier.
A# Area Fault
Default: Blank
A# Force Armed
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
Default: Blank
Activates whenever a controlled (P## Type 1, 2, 3
only) Perimeter or Interior point is faulted. The relay
remains active until all Perimeter and Interior points in
the area are normal.
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
This relay activates when this area is Force Armed. It
remains active until the area disarms or the control
panel resets.
Keyswitch area armed status with
LEDs: Use a D8129 Module and connect
If Force Bypassing is required during
Perimeter Arming, this relay does not
activate.
an LED to indicate that the area is not
ready to arm.