D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 38
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Points programmed for instant alarm
A# FA Bypass Max
response generate alarms immediately,
Default: 1
even during exit delay. To avoid instant
alarms on points adjacent to the
Selection:
0 to 99
perimeter when leaving the area,
program P## Type as 3 (Interior
Specify the maximum number of combined
Controlled points that can be faulted or bypassed
when arming this area.
Follower).
For SIA CP-01 Compliance
Refer to the prompts P## FA Retrnable and P## BA
Retrnable in Section
The Exit Delay Time must be between 45 sec and
255 sec.
4.2 Point Responses on page
92 for returning a point to the system when the point
returns to normal or when the area is disarmed.
A# Auto Watch
Users can bypass more points than the
number entered here during the
disarmed state. It is only when the user
attempts to Bypass Arm an area (or
areas) that this restriction is enforced.
Default: No
Selection:
Yes or No
Yes When the area is disarmed, Watch
Mode turns on automatically.
A# Delay Res
No When the area is disarmed, Watch
Mode must be turned on or off
manually.
Default: No
Selection:
Yes or No
Controlled points must be programmed
Yes Point Restoral Report is not sent until
the bell time expires or user
acknowledges alarm condition.
as P## Watch Point to generate a
watch tone.
No Restoral Reports are sent when point
restores, regardless of bell time.
A# Verify Time
Default: 60
A# Exit Tone
Selection:
10 to 60 (in 1-sec increments)
Default: Yes
Use alarm verification with smoke detectors to reduce
the number of false fire alarms. When Verify Time is
programmed, the control panel can check smoke
detector point activations before generating alarm
signals.
Selection:
Yes or No
Sounds an exit tone during exit delay at all keypads
assigned to this area.
You can turn off exit tones for individual
keypads by programming the
appropriate CC# 1 to 8 as No in CC#
Exit Tone.
A# Exit Dly Time
Default: 60
Selection:
Blank (0) to 600 ( in 5 sec
increments)
Exit delay time for this area when Master Exit or
Perimeter Exit arming.
Do not enable the Cross Point feature
in point indexes designated for Fire
points.
Check with your authority having
jurisdiction (AHJ) to determine the
maximum verification time allowed.
Points are programmed individually to activate the
verification feature. Refer to Section
4.1 Point Index
on page
88. Any resettable Fire point can activate
alarm verification for the area to which it is assigned.
Use separate area alarm-verification relays.
To enable alarm verification on a point, program
Point Index, Fire Point, Alarm Verify, and Resettable
as Yes.