D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 69
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
L## View Memory
Default: Refer to the program record sheet
Selection: Blank or E
Function
No.
Function Name
Alternate
Keystroke
9
View Event
Memory
[COMMAND][4][0]
View all memory events that occurred since the last
time the system was armed for all areas within the
scope of the keypad in this area.
L## View Pt Status
Default: Refer to the program record sheet
Selection: Blank or E
Function
No.
Function Name
Alternate
Keystroke
10 View Point Status
(Menu function
only)
View the current status of all points in the area to
which this keypad is assigned.
L## Walk Test
Default: Refer to the program record sheet
Selection: Blank or E
Function
No.
Function Name
Alternate
Keystroke
11 Walk Test [COMMAND][4][4]
Walk Test all Interior or Perimeter Controlled points in
the area to which this keypad is assigned.
The following features come with the Walk Test
Mode:
If enabled in Routing, Walk Start and Walk End
Reports are sent to the central station receiver at
the beginning and end of the test.
Battery powered control panel only. A Battery
Test runs during the whole test to ensure that the
battery capacity is capable of supporting the full
load of the control panel if AC fails.
- This test includes 2-sec Bell Test when the
Walk Test starts.
- The test ends when all points are tested or
the test times out after 20 min of no activity.
Local alarm annunciation and event printing; no
reports are sent to the central station receiver.
D1255 Keypad displays a sequential count, and
text after each point is activated and restored.
The keypad displays ALL PTS TESTED and an
All Points Tested Event is sent to the central
station receiver (if programmed) when the last
point is tested.
To Walk Test a Door point connected to a
D9210B Access Interface Module, open
the door without activating the door
sequence or allowing it to time out past
the extended shunt time.
L## Fire Test
Default: Refer to the program record sheet
Selection: Blank or E
Function Name
Function
No.
Alternate
Keystroke
12 Fiire Test [COMMAND][5][8]
Fire Walk Test all 24-hour points in the area where
this keypad is assigned.
One person can perform a Fire Walk Test without
assistance. The following features come with the Fire
Test Mode:
Battery powered control panel only. A Battery
Test runs during the whole test to ensure that the
battery capacity is capable of supporting the full
load of the control panel if AC fails.
- This test includes a 2-sec Bell Test (Fire Bell
relay) for each Fire point that is tested.
- The test ends when all points are tested or
the test times out after 20 min of no activity.
Local alarm annunciation and event printing; no
reports are sent to the central station receiver.
Automatic smoke detectors reset for all Fire
points programmed with P## Resettable as Yes.
D1255 Keypad displays a sequential count and
the text for the point after each point is activated
and restored.
If enabled in Routing, Walk Start and Walk End
Reports are sent to the central station receiver at
the beginning and end of the test.
A# Verify Time for Fire points that is
programmed with Yes for P## Alarm
Verify is ignored during the Fire Walk
Test.