Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 51
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
2.10 Keypad (Command Center)
This programming module contains three programming categories: Cmd Cntr Assignment, Area Text, and
Custom Function.
2.10.1 Keypad (Command Center) Assignment
This programming category assigns a keypad to an area and determines if the keypad is supervised. The
keypads are connected to the control panel using a two-wire serial data interface (SDI) bus.
This bus can support up to eight supervised keypads, each with its own unique keypad address (CC) and
corresponding DIP switch address settings. If the keypads are not supervised, you can install multiple keypads
with the same DIP switch address setting for up to 32 unsupervised keypads.
Cmd Center
Default: 1
Selection:
1 to 8
DIP Switch Setting
SDI
CC#
Address
Number
1 2 3 4 5 6
1 1 ON ON ON ON -- ON
2 2 OFF ON ON ON -- ON
3 3 ON OFF ON ON -- ON
4 4 OFF OFF ON ON -- ON
5 5 ON ON OFF ON -- ON
6 6 OFF ON OFF ON -- ON
7 7 ON OFF OFF ON -- ON
8 8 OFF OFF OFF ON -- ON
Enter the keypad (CC) number for the SDI address you are programming. This number corresponds to the DIP
switch address settings shown.
CC# Supervised
Default: Refer to the program record sheet
Selection:
Yes or No
Ye
s
Only one keypad can be installed for this CC
SDI address.
No More than one keypad can be installed using
this CC SDI address with the same address
DIP switch setting.
Supervise this SDI address and generate Trouble SDI
Reports and local trouble annunciation if a problem
occurs with this keypad or the SDI bus.
To meet UL 864 requirements, set CC#
Supervised to Yes for the fire
annunciation keypad.
Keypads that share the same address
setting display the same text and emit the
same tones, regardless of which keypad’s
keys are pressed.
Trouble SDI # Reports are always
reported as Area 1, Account 1 Events
regardless of the area the SDI device is
assigned.
When this prompt is Yes, you cannot
have duplicate DIP switch settings.
When a D1260 Alpha V Keypad is
assigned to a keypad address, you must
program CC# Enhanced Command
Center as Yes.