Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 54
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
CC# Trouble Tone CC# Exit Tone
Default: Yes Default: Yes
Selection:
Yes or No
Selection:
Yes or No
Yes Panel-wide trouble tones sound and
visual displays show at this keypad.
Yes This keypad sounds entry tones.
No This keypad does not sound entry
tones.
No Panel-wide troubles do not sound.
Visual displays still show.
Determines whether this keypad, or any keypad with
the same address setting, emits the exit delay tone
during the delay arming of an area(s). Any keypad
with a scope to arm this area can initiate the exit tone
sequence.
Determines whether this keypad, or any keypad with
the same address setting, emits the panel-wide
trouble tones (power, phone, SDI bus, and Zonex
bus).
This prompt allows you to manage the tone by
keypad. Exit Tone can also be turned off when
programming A# Exit Tone in Area Parameters.
To meet UL 864 requirements, set CC#
Trouble Tone to Yes.
The cadence and pitch of the exit tone increase for
the last 10 sec of the exit delay time.
Panel-wide trouble tones do not include
Point Troubles, Buzz on Fault, or Close
Door Now.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
CC# Entry Tone
Default: Yes
Selection:
Yes or No
Yes This keypad sounds entry tones.
No This keypad does not sound entry
tones.
Determines whether this keypad, or any keypad with
the same address setting, emits the entry delay tone.
Any Delay point within the area scope of this keypad
starts the entry sequence.
This prompt allows you to manage the
tone by keypad. Entry Tone can also be
turned off when programming your P##
Entry Tone off in Point Index.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
For SIA CP-01 Compliance
CC# Entry Tone can be set to Yes or No.
This SIA CP-01 required feature is not
supported on the D720 and D720B
Keypads.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
For SIA CP-01 Compliance
CC# Exit Tone can be set to Yes or No.
CC# Arm Now Warn
Default: No
Selection:
Yes or No
Yes This keypad activates a tone and
displays PLEASE CLOSE NOW.
No This keypad does not activate the
tone or display PLEASE CLOSE
NOW.
Determines whether this keypad sounds a tone and
displays the PLEASE CLOSE NOW warning on the
keypad when a Closing Window activates, indicating
the area automatically arms soon.