D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 94
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
P## Entry Delay
P## Ent Tone Off
Default: Refer to the program record sheet
Default: No
Selection: 5 sec to 600 sec
Selection: Yes or No
Use this option to enter the amount of entry delay
time that a user has after faulting a Controlled point
(P## Type 1, 2, 3) with a delayed response (D) (P##
Pt Response) of 4, 5, 6, 7, or 8. DISARM NOW
appears for the duration of the time programmed
when the point is faulted in the delay condition.
Disables the entry delay tone when
this perimeter point is faulted.
Yes
This is intended for use with points
set to P## Type 1 (Perimeter).
A tone sounds at keypads when this
point starts entry delay.
No
The D1255 alternates between DISARM
This option enables and disables the entry delay
warning tone for this point.
NOW and the point text of the point that
caused the area to enter into entry delay.
Do not set points to No if they are actually
used to notify the user to disarm the
If this time expires before disarming, or if the point is
configured with an instant response (I), an alarm
occurs.
system. The possibility of false alarms
increases if the entry delay warning is not
used.
Make entries in 5 sec increments. The
programmer does not allow off-increment
entries.
When the control panel is in Entry Delay, entering a
valid Passcode disarms the system as soon as the
last digit of the Passcode is entered. No other keys
are required. When the control panel is in Exit Delay
or is armed, entering a valid Passcode must be
followed by the [ENTER] or [ENT] key.
If another Perimeter or Interior Follower
Delay point trips while the area is already
in entry delay, the control panel adjusts
the delay time to the Delay point with the
least amount of delay time.
When a user enters an area, a Perimeter
point is faulted and the entry delay starts.
If an interior point must fault during entry
delay to allow the user to disarm the area
at a keypad, program P## Type as 3
(Interior Follower).
For SIA CP-01 Compliance:
P## Entry Delay must be between 30 sec and
240 sec.
Entry Tone can also be turned off when
programming your CC Entry Tone, in
Section 2.10 Keypad (Command Center)
on page 51, that allows you to manage
the tone by keypad.
You might want to disable the entry tone
in high security applications where you do
not want to annunciate entry delay.
P## Silent Bell
Default: No
Selection: Yes or No
Activate the Silent Alarm Relay when
this point enters into alarm. Keypads
do not sound the alarm tone for Non-
fire points.
Yes
No
Activate either the Fire Bell relay or
Alarm Bell relay and sound the alarm
tone at keypads when this point
enters into alarm. If this is a Fire
point, it activates the Fire Bell relay
programmed in Relay Parameters.
Otherwise, it activates the Alarm Bell
relay. The amount of time and
pattern of the relay activation is
programmed by area in Bell
Parameters.
To meet UL 864 requirements, set this
parameter to No.