D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 13
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Point/User Flag
Default: Yes
Selection:
Yes or No
Yes The control panel sends a flag with
each report telling the D6500 or
D6600 to convert point numbers and
User ID numbers to COMEX format.
Refer to
Table 7 and Table 8 for
conversion information. When this
parameter is programmed Yes,
points and User ID numbers are
converted, regardless of the
programming of the D6500 or D6600
Receiver for output to the computer
system. Refer to Appendix C in the
Conettix D6600/D6100
Receiver/Gateway Computer
Interface Manual (P/N: 4998122703).
No The control panel does not send the
flag. The D6500 or D6600 outputs
point numbers as 001 to 247 (rather
than 100 to 732) and User ID
numbers as 000 to 249 (rather than
000 to F08), as indicated in
Table 7
and
Table 8.
This program item determines how point and User ID
numbers are presented at the D6500 or D6600
display, printer, and computer RS-232 output.
When Modem Format is Yes, the control panel
sends expanded Bosch Modem IIIa
2
Communication
Format reports to the D6500 or D6600. If your central
station data files are not set up for point and User ID
number reporting, you can use this program item to
convert these numbers to COMEX Reports.
When Modem Format is Yes, the control panel
sends expanded Bosch Modem IIIa
2
Communication
Format Reports to the receiver. Point/User Flag
affects Bosch Modem IIIa
2
Communication Format
data as shown in
Table 7. The Bosch Security
Systems, Inc. D6500 or D6600 Receiver adds the
leading zero in the User ID number with Point/User
Flag programmed No.
Table 7: Modem IIIa
2
Communication Format
Data - User ID Numbers
Point/User Flag
NO
Point/User Flag
YES
000 000
001 to 005 001 to 005
006 to 013 601 to 608
014 to 021 701 to 708
022 to 029 801 to 808
030 to 037 B01 to B08
038 to 045 C01 to C08
046 to 053 D01 to D08
054 to 061 E01 to E08
062 to 069 F01 to F08
070 to 249 000
Table 8: Modem IIIa
2
Communication Format
Data – Point Numbers
Point/User Flag
NO
Point/User Flag
YES
001 to 008 100 to 800
009 to 024 101 to 116
025 to 040 201 to 216
041 to 056 301 to 316
057 to 072 401 to 416
073 to 088 501 to 516
089 to 104 601 to 616
105 to 120 701 to 716
121 to 136 801 to 816
153 to 168 217 to 232
169 to 184 317 to 332
185 to 200 417 to 432
201 to 216 517 to 532
217 to 232 617 to 632
233 – 247 717 to 731