Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 44
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
To suppress reports:
Area
Use Opening/Closing Windows to suppress
reports for a specified period of time and then
automatically turn them on again.
Default: 1
Selection:
1 to 8
Use the Restricted O/C options. A Closing Report
is sent if the user is force arming, sending
duress, or bypass arming. An Opening Report is
sent if the user is disarming during an alarm
condition or unbypasses points when disarming.
If the system is normal, no Opening or Closing
Report is sent.
Enter the area number you are programming.
A# Acct O/C
Default: No
Selection:
Yes or No
Yes Send Opening and Closing Reports
by account.
For the scheduled suppression of
Opening and Closing Reports, refer to
Section 5.1.1 Opening and Closing) to
Use this selection if the control panel
sends reports to an automation
system that cannot interpret multiple
Area Opening and Closing Reports,
or if Modem Format is programmed
as No in the Phone category (BFSK
format is used and Opening and
Closing Reports are enabled).
define Opening and Closing Windows.
Account Opening and Closing Reports
Opening and Closing Reports are sent by account
when the last area in a group of areas with the same
account number(s) is armed.
Area Opening and Closing Reports
Closing Reports are sent for each area as it is armed.
The account number is also sent for each area.
An Account Opening Report is
generated when the first area in an
account is opened (disarmed). After
the Account Opening Report is sent,
disarming other areas in the account
does not generate another Account
Opening Report. An Account Closing
Report is generated only when the
last area in an account is closed
(armed). Opening and Closing
Reports for accounts do not contain
any area information.
Customizing Account Opening and Closing
Reports
You can eliminate area Opening and Closing Reports
from selected areas in the account by programming
A# Area O/C as No for those areas.
Combination Account and Area Opening and
Closing Reports
To send both account openings and closings, and
individual area openings and closings for all areas in
the account, you must:
Opening and Closing Windows
affect Account Opening and
Closing Reports: If an account
opening or closing is generated while
an Opening or Closing Window for
this area is in effect, and Disable O/C
in Window is programmed Yes, the
report is not sent. Use the same
opening and closing window times for
all areas sharing the same account
number.
Program A# Acct O/C as Yes for all areas in the
account.
Program A# Area O/C as Yes for all areas in the
account.
Closing Reports: When areas in the account are
independently armed, each area generates an Area
Closing Report. When the last area is armed, it also
generates an Account Closing Report.
Opening Reports: When the first area in the account
is disarmed, it generates an Account Opening Report
along with an Area Opening Report. When the
remaining areas in the account are disarmed, each
area generates an Area Opening Report.
No Do not send Opening and Closing
Reports by account.
Determines if this area generates Account Opening
and Closing Reports. Program this item the same for
all areas in the account.
Area Only Opening Closing Supervision Features
Use these features to supervise opening and closing
activity by area. Auto Close, Fail To Open, and Fail
To Close all work independently of the A# Acct O/C
feature. To use these features, program O/C
Windows.