A# Fail to Close
Default: No
Selection:
Yes or No
Yes Fail to Close Report is sent for this
area if the area is not armed when
the Closing Window stop time occurs.
Note:
Program an exit delay time in
Exit Dly Time.
No Fail to Close Report is not sent for
this area.
If Auto Close is programmed
Yes, a Fail to Close Report is
sent because it occurs when the
Closing Window stop time
occurred.
If Disable O/C in Window is
Yes, the Fail to Close Report is
followed by Closing Late or
F(orce) Close Late.
This item determines if a Fail to Close Report is sent
for this area. Use to determine if a user failed to arm
the area before the Closing Window expires. Normal
Opening and Closing Reports do not need to be
programmed to use this feature.
A# Restrictd O/C
Default: No
Selection:
Yes or No
Yes Restrict Opening and Closing
Reports for this area. A# Area O/C
must be programmed Yes to
generate Restricted Opening and
Closing Reports.
Note:
If a passcode is not required for
arming or disarming and this item
is Yes, the area sends only
Restricted Opening and Closing
Reports. In this case, Restricted
Reports are sent without User ID.
Opening/Closing Window does not
affect this report. Windows do not
prevent sending Restricted Opening
and Closing Reports from being sent.
Early or late designations are not
added to Opening or Closing Reports
when they are sent according to the
rules for Restricted Opening or
Closing Reports.
No Do not Restrict Opening and Closing
Reports for this area.
Regardless of programming in
Authority Levels L## Restricted O/C,
reports are not restricted in this area
when this item is programmed as No.
Note:
Was Force Armed and Forced
Close Events can still be sent to
the central station if enabled in
Routing when force arming the
system.
This item determines if this area can restrict Opening
and Closing Report activity.
A Restricted Opening Report refers to the control
panel sending an Area Opening Report only when
the area is disarmed after a non-fire alarm.
A Restricted Closing Report refers to the control
panel sending a Force Closed Report only when the
area was master armed with Controlled points that
were faulted during the arming sequence. The
sequence of reports generated by a restricted closing
is: Was Force Armed, Forced Point, and Force
Closed.