D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 25
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
UL 864 Enhanced Communication Path
Report Prioritization:
To ensure that high priority events such
as Fire Alarms are reported before any
other queued event reports, use Route
Groups 1 and 2. The lower numbered
route groups are higher priority than the
higher numbered route groups. For
example, the following route groups are
listed from highest priority to lowest
priority: RG1RG2RG3RG4.
UL 864 Enhanced Communication Path
Supervision:
To detect and locally annunciate a break
in an Enhanced Communication Path in
less than 200 sec, program no more than
two Enhanced Communication Paths in
no more than two Route Groups. Use the
following settings for both Enhanced
Communication Paths:
Path # Poll Rate: 75 sec
Path # ACK Wait: 13 sec
Path # Retry Count: 5
The poll rate entry for the backup SDI
path might need to increase because of
heavy traffic on the network or
excessive signals generated at the
same time. All Comm prompts must be
set to No.
RG# Primary Pager
Default: No
Selection:
Yes or No
This parameter determines if this route group sends
events to a numeric pager. To send events to a
numeric pager, a phone number must also be
programmed in the route group’s primary destination.
If the External Modem feature is used,
RG# Primary SDI and RG# Backup
SDI must be set to No. The control
panel supports either enhanced
communication or external modem, but
not both at the same time.
RG# Primary SDI
Default: No
Selection:
Yes or No
This parameter determines if the primary destination
for Route Group 1 (2, 3, or 4) is sent to the NIM
RG# Backup SDI
Default: No
Selection:
Yes or No
This parameter determines if the backup destination
for Route Group 1 (2, 3, or 4) is sent to the NIM.
To completely disable Enhanced
Routing over an SDI path, RG# Primary
SDI,
RG# Backup SDI, and Enhanced
Comm prompts must be set to No.
If programming the control panel to dial a
numeric pager, choose its route group
carefully. Place events being sent to a
central station in a route group class with
a lower number than the numbers of the
events in the route group for the numeric
pager.
2.4.3 Numeric Pager Capability
The D9412GV2 and D7412GV2 Control Panels can
send most events to a numeric pager. Any time an
event is generated and routed to a numeric pager,
the control panel calls the numeric pager once for
each message in the queue. To enable the pager,
program the primary phone number and the backup
phone number to the numeric pager’s phone number
in any of the four route groups. Then select which
events to route to the numeric pager within the
selected route group.
Up to four event fields can be shown in the pager
message. Refer to
Figure 1.