D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 79
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Relay functions that resume the proper state
within one minute:
A# Fire Bell
Default: A
Alarm Bell Perimeter Fault
Summary Fire Summary Trouble
Area Armed Reset Sensors
Fire Bell AC Fail
Summary Alarm Phone Fail
Silent Alarm Summary SupBurg
Area Fault Battery Trouble
Summary Fire Tbl Communications Fail
Watch Mode Summary SupFire
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
This voltage output relay activates and provides
12 VDC output when a Fire point (P## Fire is Yes)
assigned to this area activates an alarm.
Relay functions that must be reset manually
with Change Relay function (COMMAND 54):
Fail To Close Force Armed
Duress Log % Full
2.13.1 Area Relays
Each area can be assigned a unique relay number for
each of the events listed in this section.
Area
Default: 1
Selection: 1 to 8
Enter the area number you are programming.
A# Alarm Bell
Default: A
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This voltage output relay activates and provides
12 VDC output when a Non-fire point (P## Fire is No)
assigned to this area activates an alarm.
A# Burg Time and A# Burg Pat must be
programmed in Area or Bell Parameters.
This relay activates according to the bell
pattern and remains active until the bell
time expires or a valid passcode is
entered. P## Silent Bell must be No for
the bell to ring upon alarm.
For SIA CP-01 Compliance:
Do not set A# Alarm Bell to blank. This feature is
required for SIA CP-01 compliance.
Fire Time and Fire Pat must be
programmed in Bell Parameters. This
relay activates according to the bell
pattern and remains active until the bell
time expires. P## Silent Bell must be No
in order for the bell to ring upon alarm.
Although Relay C is a valid entry for A#
Fire Bell, do not program Relay C for this
entry. Use Relay A for the A# Fire Bell.
To meet UL 864 requirements, set A#
Fire Bell to a value other than Blank.
A# Reset Sensors
Default: C
Blank, 1 to 128 (1 to 64 for
Selection:
D7412GV2), A, B, or C
Unlike the default relay for Alarm Bell and Fire Bell,
this voltage-output relay (Relay C) de-activates for
5 sec when the Reset Sensors? function is activated
from the keypad or during a Fire Walk Test.
The Reset Sensors time converts from
the
5 sec default time to the time
programmed in A# Verify Time (Section
2.9 Area Parameters on page 5) when a
point programmed for P## Alarm Verify
(Section 4.1 Point Index on page 88)
enters an alarm condition.