D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 105
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
CMD9 Point Index
Default: 31
Selection: Blank (00) to 31
This entry selects one of the 31 P## Index codes that
define how the control panel reacts when a
COMMAND 9 is initiated.
The point index code used for
COMMAND 7 and COMMAND 9 must not
be used for any other points on the
system.
If the point index for COMMAND 9 has
Fire points programmed as Yes, this
causes access control doors to unlock if
Fire Unlock is also programmed as Yes.
Refer to the D9210B Program Entry
Guide
(P/N: 32207).
CMD9 BFSK/Relay
Default: 1
Selection: 0 to 9
The value in this entry selects one of the digits shown
for reporting in BFSK or for activating relays 73 to 80
(on the D9412GV2) or relays 9 to 16 (for the
D7412GV2) when a COMMAND 9 is initiated (refer to
the P### BFSK/Relay prompt in Section
4.3 Point
Assignments
on page 103).
COMMAND 9 does not activate the
Summary Fire Alarm relay.
CMD9 Point Text
Default: [COMMAND][9]
Up to sixteen alphanumeric
Selection:
characters
Enter alphabetic characters (A to Z) in capital letters
Enter up to sixteen characters of text to describe the
point. This point text is displayed at keypads (if the
point is programmed as visible) and sent to the D6500
or D6600 when transmitting in Modem IIIa
2
format (if it
is a reporting point).