D9412GV2/D7412GV2 | Program Entry Guide | 6.0 GV2AUX EN | 143
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Table 43: Cross Point Ranges Within Groups
Cross Point
Group
Point Range
1 1 to 8
2 9 to 16
3 17 to 24
4 25 to 32
5 33 to 40
6 41 to 48
7 49 to 56
8 57 to 64
9 65 to 72
10 73 to 80
11 81 to 88
12 89 to 96
13 97 to 104
14 105 to 112
15 113 to 120
16 121 to 127
17 129 to 136
18 137 to 144
19 145 to 152
20 153 to 160
21 161 to 168
22 169 to 176
23 177 to 184
24 185 to 192
25 193 to 200
26 201 to 208
27 209 to 216
28 217 to 224
29 225 to 232
30 233 to 240
31 241 to 247
Refer to Section 2.3 Routing on page 15 for
information about programming the destination (for
example, the central station) for Unverified Events. An
Unverified Event does not produce a corresponding
Restoral Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or trouble
conditions. Points programmed with point response D
(Delayed) eventually enter into an alarm condition if
the area is not disarmed in time.
Cross Point Time
Default: 20 sec
Selection: 5 sec to 255 sec
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.