Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 14
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
2.2.1 Special Point/User Reporting
Phone Supv Time
Independent Zone Control Notice: When using
Independent Zone Controls (IZC) to send
Opening/Closing Reports by point, do not duplicate
reporting independent point numbers with User ID
Reports (refer to Section
Default: Blank
Selection:
Blank or 10 to 240
3.1 Pass Code or Token
Worksheet
Blank No phone line supervision.
on page 84). For example: If an IZC is
connected to Point 8, do not use User ID 8.
10 to 240 Enter the number of seconds (in 10
sec increments) you wish to wait
before indicating trouble. After a
faulted phone line restores, it takes
the same amount of time to start
restoral responses.
D6000: Opening/Closing User ID numbers are
identified at the receiver as ZONEs (same
identification as independent points). Refer to
Table
9
.
Table 9: D6000 User IDs and Zones
Phone line trouble responses: Keypads display
SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if Buzz on
Fail is Yes and CC Trouble Tone is Yes.
Zone
Zone
User ID
Number
User ID
Number
With dual phone lines (using the D928 Module), the
restored phone line handles all messages regardless
of the phone line’s number.
1 B 91 1
2 C 92 2
3 D 93 3
Phone, Trouble, and Restoral Events report when
they occur. They report also when a Diagnostic
Report is initiated from a keypad or by a Sked.
4 E 04 4
5 F 95 5
6 6 96 0
7 7
To meet UL 864 requirements, set this
8 8
parameter to a non-zero value.
D6500 or D6600 Receiving BFSK Format:
Opening/closing User ID numbers are identified at
the receiver as ZN (same identification as
independent points). The ZN numbers are based on
the tens digit of the User ID number. This applies
only for Users 000 through 099. Users 100 through
249 do not report in BFSK format.
Alarm On Fail
Default: No
Selection:
Yes or No
Yes Generate alarm responses when a
phone line fails.
DTMF Dialing
Default: Yes
Selection:
Yes or No
Yes Dials the programmed phone
number(s) using DTMF.
No Pulse dialing only.
Use dual-tone multi-frequency (DTMF) to dial the
central station receiver phone number(s) for event
reports, or to dial the remote programming software
(RPS).
No Phone failures report as trouble
responses for Area 1 or the account
number associated with Area 1.
To meet UL 864 requirements, set this
parameter to No.
Phone Supv Time must be programmed
to use this feature.
Phone Failure Alarm Responses: The Alarm Bell
relay for Area 1 activates. All Phone Event messages
report as Area 1 and the account number for Area 1.