D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 76
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
2.11.5 Access Control Levels
Burglar bells are silenced in the local area
when a user disarms with a token or card
L## Security Level
Default: Refer to the program record sheet
Selection: M, P, D, or Blank
M Users have access rights for this
area when the area is in any armed
state.
P Users have access rights for this
area when the area is Perimeter
Armed or Disarmed but not while the
area is Master Armed.
D Users have access rights for this
area only while it is disarmed.
Blank Users do not have access rights to
this area.
Security Level [TOKEN FUNCTION]
When the user presents a token or card at the reader,
access is granted only when the user has the
authority to enter the area under certain armed
conditions.
L## Disarm Level
Default: Refer to the program record sheet
Selection: I, D, or Blank
I
Users change the Master Armed
state and Perimeter Armed state to
Perimeter Instant. The armed state
does not change in other areas, and
the armed state does not change if
the area is already in the perimeter
instant or disarmed state. User
needs access level for Master
Armed (M) state.
D
Users change the local area’s
Master Armed state and Perimeter
Armed state to the Disarm state.
User needs access level for Master
Armed (M) or Perimeter Armed (P)
state. All areas within the scope of
the keypad assigned to the D# CC#
Scope in the access handler, and
areas to which the user has disarm
rights, disarm as programmed.
Blank
Users do not have disarm rights in
this area.
or presents the token or card during an
alarm. The user must use a pass code to
silence a Fire Bell. Cancel Reports are
sent after a valid pass code or token or
card silences the bell.
Opening and Closing Reports are sent to
the central station receiver if programmed.
For more information on programming
this prompt for a shared area, refer to
Access Control Readers Assigned to the
Shared Area in Section 2.9.3 Shared-
Area Characteristics on page 41.
L## Function Level
Default: Refer to the program record sheet
Selection: M, D, C, or Blank
Activate the custom function
assigned to the door in this area
while the area is Master Armed or
Disarmed only.
M
Activate the custom function
assigned to the door in this area
while the area is Disarmed only.
D
User can activate the custom
function assigned to the door in this
area while the area is Master Armed,
Perimeter Armed or Disarmed.
C
User cannot activate the custom
function assigned to the door in this
area.
Blank
When a token or card can also disarm an
area, the custom function starts after the
area disarms.
A user does not require L## Security
Level or L## Disarm Level authority to
activate a custom function with a token or
card.
Tokens or cards that are used to execute
Custom Functions must have a pass
code assigned to the correspoinding
User###.