Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 18
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Fire Reports Burglar Reports
Select Yes to send a report when the event occurs.
To meet UL 864 requirements for
Central Station and Remote Station
applications, enable Fire Reports.
Table 11: Burglar Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 10: Fire Reports
Report
Selection
s
Report Description
R# Fire Alarm Yes, No Fire Event
R# Fire
Restore
(Alarm)
Yes, No
Fire restoral from
alarm
R# Fire
Missing
Yes, No Missing Fire point
R# Fire
Trouble
Yes, No Fire trouble
R# Fire
Supervis
Yes, No Fire supervision
R# Fire
Restore
(T/M/S)
Yes, No
Fire restoral from
trouble, missing, or
bypass
R# Fire
Cancel
Yes, No Canceled fire alarm
R# Fire Sup
Miss
Yes, No
Fire supervisory
missing
R# Fire Supv
Rest
Yes, No
Restorals from Fire
Supervision
This event is not reported when using BFSK format.
Report Selections Report Description
R# Alarm Yes, No Burglar Alarm Event
Yes, No
R# Burg
Restore
Non-fire restoral from
trouble, missing, or
supervisory
R# Duress Yes, No Duress
Yes, No Missing Alarm point
R# Missing
Alarm
Yes, No User code tamper
R# Usr Code
Tmpr
Yes, No Trouble Event
R# Trouble
Rpt
Yes, No
R# Missing Missing Trouble
Trbl Event
Yes, No
R# Non Fire
Suprv
Non-fire Supervision
Event
Yes, No Point bus failure
R# Pt Bus
Fail
Yes, No
R# Pt Bus
Rstl
Restoral of point bus
after failure
Yes, No
R# Non Fire Canceled non-fire
Cncl alarm
Yes, No
R# Alarm
Restore
Non-fire restoral from
alarm
Yes, No Supervisory missing
R# Sup
Missing
R# Unverified
Evt
Yes, No
Unverified Events for
Cross Points
R# Unverified Evt is not reported when using BFSK
format. Additionally, this event does not produce a
corresponding Restoral event.
R# Unverified Evt is sent when a single
point programmed in Cross Point Group
faults into an alarm condition, then
restores before the Cross Point Time
elapses.
R# Unverified Evt encompasses both
Fire and Non-fire points, but is not related
to the A# Verify Time used for smoke
detectors.
The 9000GV2 Series control panels log a
Ground Fault Event as Trouble Point 256.