Bosch Appliances D9412GV2 Video Game Controller User Manual


 
D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 30
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Bat Fail/Res Rpt
AC Tag Along
Default: Yes
Default: Yes
Selection:
Yes or No
Selection:
Yes or No
Yes Send AC messages as tag along
events.
No Do not send AC messages as tag
along events.
Send AC Reports only if any other event occurs while
AC is off-normal.
If AC Tag Along is set to Yes and a
subsequent event is generated, the AC
Fail Event is sent first, before sending
any subsequent events.
AC Tag Along is required for NFPA
and UL 864 Commercial Fire systems.
Be sure to program AC Fail/Res Rpt as
No if AC Tag Along is programmed
Yes.
AC/Battery Buzz
Default: No
Selection:
Yes or No
Yes Initiates panel-wide trouble tone at
all keypads.
No Does not initiate panel-wide trouble
tone at keypads
Initiates a panel-wide trouble tone at keypads when
AC fails or battery is low or missing. This program
item does not prevent the SERVC AC FAIL or
SERVC BATT LOW displays.
To comply with NFPA standards and
UL 864 requirements for Commercial Fire
systems, program this item as Yes.
If annunciating panel-wide troubles at a
keypad with CC# Scope set to Panel
Wide is undesirable, set CC# Trouble
Tone to No. Refer to Section 2.10
Keypad (Command Center) on page 51
for keypad configurations.
Battery Failure and Restoral Reports are
sent to the central station. They are routed
to the telephone number programmed for
Power/Phone Events.
Yes
Missing or
shorted
BATTERY
MISSING
Modem
Report
s
Discharged
below 12.1
VDC
BATTERY
LOW
Missing,
shorted low
battery
TROUBLE
ZONE 9
BFSK
Report
s
No Battery Failure and Restoral Reports are not
sent to the central station.
To comply with NFPA standards and
UL 864 requirements for Commercial Fire
systems, program this item as Yes.
2.6 Printer Parameters
Up to three D9131A Parallel Printer Interface
Modules can be connected to the D9412GV2’s (one
printer for the D7412GV2’s) SDI bus. Each printer is
identified by an address of 17, 18, or 19. Options are
available for Routing Reports and area assignments.
Printer Address
Default: 17
Selection:
17, 18, or 19 (only 17 is available
for the D7412GV2)
Enter the printer address you are programming.
P## Area Assign
Default: 1
Selection:
1 to 8
Assign an area to the printer programmed in Printer
Address.