D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 94
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
When a point programmed for P## Silent
Bell is faulted, the timer for the A# Burg
Time starts, even though the bell is not
yet ringing. As much as 3 min can elapse
before the second attempt fails. Ensure
that A# Burg Time is programmed to
provide the amount of bell time you need,
minus the additional 3 min that might
elapse before the bell actually begins to
ring.
P## Invisible Point
Default: Refer to the program record sheet
Selection: Yes or No
Yes
Keypads do not display alarm
activity from this point.
No
Activity from this point is visible at
the keypads.
To meet UL 864 requirements, set this
parameter to No.
Use this option to determine whether the point
appears in the keypad display upon an alarm
condition. For LED keypads, the LED does not
illuminate upon an alarm condition. Point text
appears and annunciation is made for Invisible points
programmed for a trouble condition in point response.
To prevent the keypad alarm tone and the
A# Burg Alarm bell from sounding,
program P## Silent Bell as Yes.
If a user enters a valid passcode while a
bell is ringing for an invisible alarm, the
keypad shows ALARM SILENCED.