1.3 Guide to UL 864 Programming Requirements
This section identifies the programming requirements you must make in order to comply with UL 864
Commercial Fire applications.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 3.
Table 3: UL 864 Programming Requirements
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Refer to
Page:
If using two phone lines:
Phone 1 through 4 Yes 24 characters
Program a valid phone
number
12
Phone Supervision Yes 0 to 240 sec 10 to 200 sec 16
Alarm On Fail No Yes / No Set to No 16
Buzz On Fail Yes Yes / No Set to Yes 16
Two Phone Lines Yes Yes / No
Set to Yes when using
PSTN communications.
16
Expand Test Report Yes Yes/No Set to Yes 17
Fire Reports Yes Yes / No Set to Yes 21
R# Fire Supervisory
Missing
Required Yes/No Set to Yes 21 (Table 9)
Test Reports Yes Yes / No Set to Yes 22
AC Fail Report Yes Yes / No Set to Yes 23 (Table 13)
AC Restoral Report Yes Yes / No Set to Yes 23 (Table 13)
Battery Missing Report Yes Yes / No Set to Yes 23 (Table 13)
Low Battery Report Yes Yes / No Set to Yes 23 (Table 13)
Battery Restoral Report Yes Yes / No Set to Yes 23 (Table 13)
R# Service Start Report Required Yes / No Set to Yes 26 (Table 17)
R# Service End Report Required Yes / No Set to Yes 26 (Table 17)
R# Fire Walk St Report Required Yes / No Set to Yes 26 (Table 17)
R# Fire Walk End Report Required Yes / No Set to Yes 26 (Table 17)
R# Walk Test St Report Required Yes / No Set to Yes 26 (Table 17)
R# Walk Test End Report Required Yes / No Set to Yes 26 (Table 17)
AC Fail Time Yes 1:00 to 90:00 min Enter 1:00 29
AC Fail Display Yes 10 to 300 sec 10 to 200 sec 29
AC Tag Along Yes Yes / No Set to Yes 29
AC/Battery Buzz Yes Yes / No Set to Yes 30