Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 102
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Keypad Programming of P### Point Index
D1255
1. Refer to Figure 1 on page 7 to access Keypad
Programming and navigate to the POINT
PARAMETERS option. The PT NUM 1 - ###
option shows.
2. Enter the point number you wish to configure and
press [ENT].
3. The keypad shows the point number and the
index number (for example, INDEX: 3).
4. Press [ENT]. An invisable editing cursor is
enabled for point index number.
5. The [PREV] button acts as a [Backspace] key.
Press [PREV] to delete the characters of the
index number, and then enter the new index
number.
The keypad does not accept invalid index
numbers.
6. Press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your
selection has been configured.
D1260
Press [ENT] to save the changes
1. Refer to Figure 2 on page 8 to access Keypad
Programming and navigate to the Point
Parameters option.
2. Press [ENTER]. The Point Num 1 – 247 (1 – 75
for a D7412GV3) option shows.
3. Enter the point number you wish to configure and
press [ENTER]. The keypad reads Point# Index,
and then the currently configured index number
(for example, Point (1) Index: 3).
4. Press the Edit softkey to change the point index.
5. The Backspace softkey allows you to erase
characters. The Clear softkey allows you to clear
the entire index number. Use the softkeys and
the number buttons on the keypad to enter the
new point index number.
6. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection has been configured.
P### Area Assign
Default: 1
Selection: 1 to 32 for D9412GV3
1 to 8 for D7412GV3
Select the area number to which the point is
assigned.
P### Debounce
Default: 2
Selection: 1 to 15
1 .300 sec
2 .600 sec
3 .900 sec
4 1.2 sec
5 1.5 sec
6 1.8 sec
7 2.1 sec
8 2.4 sec
9 2.7 sec
10 3.0 sec
11 3.3 sec
12 3.6 sec
13 3.9 sec
14 4.2 sec
15 4.5 sec
The debounce count is the number of times the
control panel scans a point before generating an
alarm. Scan cycles are 300 ms.
For appropriate settings consult the manufacturer’s
instructions for the device connected to this point.
Use an entry of two or higher. Interior
Follower points need a Debounce value
of at least three.
Door points assigned to D9210B modules