Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction EN | 11
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Table 3: UL 864 Programming Requirements (continued)
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Refer to
Page:
For IP Communications to a D6600 Receiver
Enhanced Comm Yes Yes / No Set to Yes 131
Path1 IP Add1 (2, 3 or 4) Yes 000 to 255
Program a valid IP
address
131
Path 1 Poll Rate Yes 0, 5 to 65535 sec* Program as necessary 132
Path 1 Ack Wait Yes 0, 5 to 65535 sec* Program as necessary 135
Path 1 Retry Count Yes 0 to 255 Program as necessary 135
SDI 88 Supervision Yes Yes / No Set to Yes 136
For Ground Fault Enable Switch
(Refer to the
D9412GV3/D7412GV3
Operation and Installation
Guide (P/N:
F01U143070)
Yes Closed = Enabled
Open = Disabled
Closed N/A
* Set the Path 1 Poll Rate to 65535 for 24 hr.
The following programmable parameters are recommended by Bosch when installing a commercial fire alarm
system. Always check with your local Authority Having Jurisdiction.
Table 4: UL 864 Programming Recommendations
Prompt Possible Settings Recommendation
Phone Line Fail Report Yes / No Yes
Phone Line Restoral Report Yes / No Yes
Fire Walk Start Report Yes / No Yes
Fire Walk End Report Yes / No Yes
Cancel Report Yes / No Yes
CC# Scope
Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Do not program No Keypad
CC# Enhanced Command
Center
Yes / No Set to Yes, if applicable
CC# Menu Key Lock Yes / No If using D1256RB, set to No
Reset Sensors Disable/Enable/Passcode Protect Enable
Fire Test Disable / Enable / Passcode Protect Enable
L## Reset Sensors Disable / Enable
If Reset Sensor is set to Passcode
Protect, set this to Enable
L## Fire Test Disable / Enable
If Fire Test is set to Passcode
Protect, set this to Enable
U### User Group 0 to 8 Program as 0
P## Ring Until Restored Yes / No
May be required for Waterflow,
otherwise No
P## Cross Point Yes / No Set to No for Fire devices.
D# Fire Unlock Yes / No No