Bosch Appliances d9412gv3 Video Game Controller User Manual


 
D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 85
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
User ###
Default: 001
Selection:
000 or 001 to 249 (001 to 099 for
the D7412GV3)
Enter the User number you are programming.
User 000 is the Service Authority Level
(Level 15). You cannot change the
programming for user 000.
Only the Service Authority Level (User
000) can delete User 000. When a user
other than User 000 tries to delete the
passcode for User 000, the keypad
displays NOT IN USE.
User 000 cannot be added or changed
at the keypad whether it exists or not.
U### Passcode
Default: Refer to the program record sheet
Selection: Three to six digits ( 0 to 9)
Enter three to six digits to enable a passcode for the
master user in this group.
To meet UL 864 requirements, enter at
least one Passcode.
User I.D.000 is the reserved user for
service personnel. The default service
passcode is 123.
The programmer does not allow you to
enter any passcode number that might
conflict with a duress passcode. The
programmer reserves the passcode
number plus 1, duress passcode number
plus 2, passcode-number minus 1, and
passcode number minus 2.
For example, when a passcode of
654321 is entered, 654322, 654323,
654320, and 654329 are reserved and
are not available to other users.
The authority to silence a bell is granted
to all passcodes regardless of their
authority level assignments. A user
passcode can silence a Fire or Burg bell
as long as any authority level is assigned
to the area where the bell can be
silenced.
U### User Group
Default: 0
Selection: 0, 1 to 8
Create a group of up to 249 users (99 for the
D7412GV3) whose combinations can be enabled and
disabled using an automatic user window. This is the
number entered into the W# User Group for any
active W# User Window. Multiple windows can be
programmed for one user group (up to eight) within
one 24-hour period. For example, if User Group 1
has a window running from 8:00 AM (start time) to
4:00 PM (stop time), the users for that group can use
their passcodes only between that time. Between
4:00 PM that day and 8:00 AM the next day, the
users cannot use their passcodes.
To enable this user’s passcode at all
times, leave U### User Group 0.
User Group Window times cannot be changed from
the keypad. When a window is assigned to a user
group, the users in that group rely on the window to
be active (within the start and stop times) for their
passcodes to function. The only way to disable the
window is by reprogramming the control panel from
the remote programming software (RPS).
U### Area 1 [through Area #] Auth
Default: Refer to the program record sheet
Selection: 0 to 14
Assign an authority level to the user for this area.
A setting of 0 means the user has no authority in this
area.
To meet UL 864 requirements, assign a
valid authority level to the Passcode to
silence bells.