CC# Supervised
Default: Refer to the program record sheet
Selection:
Yes or No
Yes Only one keypad can be installed for this
CC SDI address.
No More than one keypad can be installed
using this CC SDI address with the same
address DIP switch setting.
Supervise this SDI address and generate Trouble
SDI Reports and local trouble annunciation if a
problem occurs with this keypad or the SDI bus.
To meet UL 864 requirements, set CC#
Supervised to Yes for the fire
annunciation keypad.
Keypads that share the same address
setting display the same text and emit the
same tones, regardless of which keypad’s
keys are pressed.
Trouble SDI # Reports are always
reported as Area 1, Account 1 Events
regardless of the area the SDI device is
assigned.
When this prompt is Yes, you cannot
have duplicate DIP switch settings.
CC# Enhanced Command Center
Default: No
Selection:
Yes or No
Yes This keypad is a D1260 Series
Keypad.
No This keypad is not a D1260 Series
Keypad.
When a D1260 Series Keypad is installed at this
keypad address, this item must be set to Yes.
Keypad Programming of CC# EnhancCMDCTR
D1255
1. Refer to Figure 1 on page 7 to access Keypad
Programming and navigate to the COMMAND
CENTER option.
2. Press [ENT]. The CC NUM 1 – 16 option shows.
3. Enter the keypad number you wish to configure
and press [ENT]. The keypad reads CC#
SCOPE, and then the current configuration (for
example, PANEL WIDE).
4. Press [NEXT]. The current keypad type shows
(for example, CC - 1 TYPE ENHANCED: YES).
5. Press [ENT] to change the keypad’s type.
6. Press [NEXT] or [PREV] to toggle to No to
indicate that the D1255 is not an enhanced
keypad, and then press [ENT] to save the
changes.
When the keypad reads PARAMETER SAVED, your
selection has been configured.
D1260
1. Refer to Figure 2 on page 8 to access Keypad
Programming and navigate to the Command
Center option.
2. Press [ENTER]. The CC Num 1 – 16 option
shows.
3. Enter the keypad number you wish to configure
and press [ENTER]. The keypad reads CC#
Scope, and then the current configuration (for
example, Panel Wide).
4. Press the Type softkey. The current keypad type
shows (for example, CC (1) Type Enhanced:
Yes).
5. Press the Edit softkey to change the keypad’s
type.
6. Press the Yes or No softkey, and then press the
Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection has been configured.
Reboot the system to enable a D1260
Series Keypad.
To reboot the system, close and open the
reset switch, labeled “S1 RESET,”
located in the upper right corner of the
control panel.
CC# Area Assign
Default: 1
Selection:
1 to 32 on D9412GV3
1 to 8 on D7412GV3
Enter the area number where you are installing this
keypad or keypads with this address and the same
DIP switch settings.