2.1.1 User Groups
For the D9412GV3, there are 249 groups (99 groups
for the D7412GV3) consisting of one user with a
passcode and token (master) and three users with
tokens or cards but not a passcode (sub-user). All
users in the group share the same authority level as
the master user.
2.1.2 Passcodes
In a control panel with factory default settings, only
the master user has an assigned passcode. A
passcode can be three to six digits. Entering three
digits in User ### chooses the user. Programming
the U001 Passcode assigns a passcode to the
master user. Sub-users cannot use the passcode. Do
not assign tokens or cards to User ID 0 (zero), which
is reserved for the service passcode.
Passcode Tamper
If a user enters six consecutive invalid passcodes at
the same keypad, the control panel sends a User
Code Tamper report to the central station. The invalid
passcode count resets when a valid passcode is
entered at the same keypad. Refer to R# Usr Code
Tamper in Table 10 on page 21 for information on
enabling this report.
The passcode tamper condition is also reported in a
manually initiated Extended Test Report and to RPS
through control panel diagnostics. As a result, the
tamper condition is reset after the successful
completion of a manual report or when disconnecting
from an RPS session. The tamper condition is not
reset when the control panel reboots.
2.1.3 User Group Window
Use U### User Group to enable and disable the
U### Passcode for up to eight different time periods
throughout the day. Assign the number (1 to 8)
programmed in U### User Group to a User
Windows #. If the user is outside a window,
COMMAND DISABLED appears on the keypad after
the user enters the passcode and presses [ENTER].
This window does not affect tokens and
cards. It only affects the passcode of the
master user.
When using the Add/Change User
function at the keypad, the authority levels
and the changes made affect the master
user’s passcode and the entire group’s
token or cards.
When using the ACCESS CONTROL
LEVEL function at the keypad, the whole
group is affected by whether or not the
level is on or off for access control
functions only.
When using the DELETE USER?
function, the whole group is deleted. You
cannot delete each user within the group
individually. Use the ADD/CHG USER?
function to change a user token or card
instead of deleting the whole group.
2.1.4 User Name
Each user group can be assigned one U### Name.
This name is logged and sent to the central station
for all the users in the group. The user ID is used to
differentiate which user’s token or card was
executed.
When using a D1260 Keypad, User 249
text is used for contact information text
(such as telephone numbers). If a D1260
is installed on the system, do not use
User 249 for user ID information.
2.1.5 Tokens and Cards
The master user assigned the passcode can also be
assigned a token or card by programming the U###
Mstr Site and U### Mstr Crd Data.
Three more tokens or cards are assigned to the user
group for sub-users using the U### SU# Site and
U### SU# C/D.