D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 53
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
CC# Enter Key Relay
Default: 0
Selection:
0 to 128, A, B, C (0 to 64, A, B, C
for the D7412GV3)
0 The [ENTER] key is not used to
activate a relay.
1 to 128 (64),
A, B, C
Assign the relay number that
activates when [ENTER] is pressed
at this keypad after the user enters
a valid passcode.
Enter Key Relay: Program the relay number that
activates momentarily for 10 sec when a user enters
a valid passcode and presses the [ENTER] key on
the keypad. Two events are generated when this
function is used: RELAY ### SET with User ID, and
RELAY ### RESET without User ID. The system
logs this action as two events.
Entering a valid code and pressing [ENTER] at a
keypad silences a ringing bell.
Using CC# Enter Key Relay for a low-level
access control strike on a door does not shunt a
point.
When programmed to activate a relay, the
[ENTER] key cannot be used for any
other function.
Relays used for this function must not be
shared with any other point, sensor reset,
control panel, or bell functions. Sharing
can cause errors in relay operation.
CC# Enter Key Cycle Door
Default: No
Selection:
Yes or No
Yes The [ENTER] key is used to cycle the
door programmed for CC Assign
Door.
No The [ENTER] key is not used to cycle
the door.
Enter Key Cycle Door: Program this prompt as Yes
to start the door cycle sequence for the door number
programmed in CC# Assign Door when a user
enters a valid passcode and presses [ENTER]. This
includes shunting the point assigned to the door.
ACCESS GRANTED prints on the local printer and at
the central station receiver, if programmed.
The service passcode cannot be used
for the CC# Enter Key Cycle Door
application.
When programmed to activate a relay,
the [ENTER] key cannot be used for
any other function.
Relays used for this function must not
be shared with any other point, sensor
reset, control panel, or bell functions.
Sharing can cause errors in relay
operation.
The door does not cycle if Enter Key
Relay is programmed.
9210 NOT READY appears at this
keypad when you press [ENTER] if the
D9210B is not programmed with a D#
Entry Area (in the Access Control
section) or if CC Assign Door does not
have a door number assigned.
CC# Assign Door
Default: No Door
Selection:
No Door, 1 to 8 on D9412GV3.
(No Door, 1, 2 on D7412GV3)
No
Door
No door controller is assigned for adding
tokens.
1 to 8 The door controller assigned to this keypad
is used to read new tokens when the Add
User Mode is initiated.
If the assigned door remains open and this keypad
has the CC# Close Door Warning Tone set to Yes,
the CLOSE DOOR # message appears on this
keypad.